Section 2 Functions
RF TAG OVERWRITE COUNT CONTROL Command with a Addition Specification
The overwrite count control area consists of 4 bytes from the specified start address. The increment
value is added to the overwrite count and then written to this area. When the value reaches 100,000
(i.e., 0186A0 hex), a warning code is returned. You can read the overwrite count control area with a
read command. If the control area data is already 100,000, the control area value will not be
refreshed, and a warning code will be returned as a response. When the refresh count is set to 0000
hex, the count will not be updated, and only an overwrite count check will be performed.
Reader/Writer Controls
RESET
You can restart the Reader/Writer.
You can restart the Reader/Writer by using a RESET command or by using a CIP message
(specifically, by issuing the Reset service to the Identity object) from a Web browser. The Reader/
Writer will return the execution results and reset itself.
If you reset the Reader/Writer during tag data link communications, the connection will be broken and must be re-
established from the originator.
Host device Reader/Writer
Host device
Reader/Writer
Reader/Writer operation
Reset
Self-reset processing
Response
Initialization
Waiting for connection