Table 1-1 (Cont.) Environmental Requirements for Oracle Exadata Database
Machine X5-2
Environmental
Component
Oracle Exadata
Database
Machine X5-2
Full Rack
Oracle Exadata
Database
Machine X5-2
Half Rack
Oracle Exadata
Database
Machine X5-2
Quarter Rack
Oracle Exadata
Database
Machine X5-2
Eighth Rack
Cooling
See Also:
"Temperature
and Humidity
Requirements
(page 1-44)",
and "Ventilation
and Cooling
Requirements
(page 1-45)"
• Extreme
Flash drives
Maximum:
52,578 BTU/
hour (55,469
kJ/hour)
Typical:
36,804 BTU/
hour (38,829
kJ/hour)
• High
capacity
drives
Maximum:
52,052 BTU/
hour (54,915
kJ/hour)
Typical:
36,437 BTU/
hour (38,441
kJ/hour)
• Extreme
Flash drives
Maximum:
28,396 BTU/
hour (29,958
kJ/hour)
Typical:
19,877 BTU/
hour (20,970
kJ/hour)
• High
capacity
drives
Maximum:
28,133 BTU/
hour (29,680
kJ/hour)
Typical:
19,693 BTU/
hour (20,776
kJ/hour)
• Extreme
Flash drives
Maximum:
14,195 BTU/
hour (14,975
kJ/hour)
Typical:
9,936 BTU/
hour (10,483
kJ/hour)
• High
capacity
drives
Maximum:
14,082 BTU/
hour (14,856
kJ/hour)
Typical:
9,857 BTU/
hour (10,399
kJ/hour)
• Extreme
Flash drives
Maximum:
11,674 BTU/
hour (12,317
kJ/hour)
Typical:
8,172 BTU/
hour (8,622
kJ/hour)
• High
capacity
drives
Maximum:
11,530 BTU/
hour (12,164
kJ/hour)
Typical:
8,071 BTU/
hour (8,515
kJ/hour)
Air flow front-to-
back (subject to
actual data
center
environment)
See Also:
"Temperature
and Humidity
Requirements
(page 1-44)",
and "Ventilation
and Cooling
Requirements
(page 1-45)"
• Extreme
Flash drives
Maximum:
Approximatel
y 2,434 CFM
Typical:
Approximatel
y 1,704 CFM
• High
capacity
drives
Maximum:
Approximatel
y 2,410 CFM
Typical:
Approximatel
y 1,687 CFM
• Extreme
Flash drives
Maximum:
Approximatel
y 1,315 CFM
Typical:
Approximatel
y 920 CFM
• High
capacity
drives
Maximum:
Approximatel
y 1,302 CFM
Typical:
Approximatel
y 912 CFM
• Extreme
Flash drives
Maximum:
Approximatel
y 657 CFM
Typical:
Approximatel
y 460 CFM
• High
capacity
drives
Maximum:
Approximatel
y 652 CFM
Typical:
Approximatel
y 456 CFM
• Extreme
Flash drives
Maximum:
Approximatel
y 540 CFM
Typical:
Approximatel
y 378 CFM
• High
capacity
drives
Maximum:
Approximatel
y 534 CFM
Typical:
Approximatel
y 374 CFM
IP Addresses
See Also:
"Network
Connection and
IP Address
Requirements for
Oracle Exadata
Database
Machine
(page 1-47)"
68 for Ethernet
network,
assuming single
cluster
Up to 36 for
InfiniBand
network
38 for Ethernet
network,
assuming single
cluster
Up to 18 for
InfiniBand
network
22 for Ethernet
network,
assuming single
cluster
Up to 8 for
InfiniBand
network
22 for Ethernet
network,
assuming single
cluster
Up to 8 for
InfiniBand
network
Chapter 1
General Environmental Requirements