Table 5-52 Threshold Values for Oracle Exadata Database Machine X3-8 Full
Rack with Three-phase, High-voltage 24 kVA PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 12 16
A Module 1, phase
2
0 13 17
A Module 1, phase
3
0 10 13
A Module 2, phase
1
0 10 13
A Module 2, phase
2
0 13 17
A Module 2, phase
3
0 11 15
B Module 1, phase
1
0 10 13
B Module 1, phase
2
0 13 17
B Module 1, phase
3
0 11 15
B Module 2, phase
1
0 12 16
B Module 2, phase
2
0 13 17
B Module 2, phase
3
0 10 13
5.3.1.8 PDU Thresholds for Oracle Exadata Database Machine X2-8 Full Rack
This section contains the PDU thresholds for Oracle Exadata Database Machine X2-8
Full Rack.
• Table 5-53 (page 5-48) Threshold Values for Oracle Exadata Database Machine
X2-8 Full Rack with Single-phase, Low-voltage 22 kVA PDU
• Table 5-54 (page 5-48) Threshold Values for Oracle Exadata Database Machine
X2-8 Full Rack with Three-phase, Low-voltage 24 kVA PDU
• Table 5-55 (page 5-48) Threshold Values for Oracle Exadata Database Machine
X2-8 Full Rack with Single-phase, High-voltage 22 kVA PDU
• Table 5-56 (page 5-49) Threshold Values for Oracle Exadata Database Machine
X2-8 Full Rack with Three-phase, High-voltage 24 kVA PDU
Table 5-53 (page 5-48) lists the threshold values for Oracle Exadata Database
Machine X2-8 Full Rack using a single-phase, low-voltage 22 kVA PDU.
Chapter 5
Configuring the Power Distribution Units