Table 5-50 Threshold Values for Oracle Exadata Database Machine X3-8 Full
Rack with Three-phase, Low-voltage 24 kVA PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 21 27
A Module 1, phase
2
0 23 30
A Module 1, phase
3
0 22 28
A Module 2, phase
1
0 20 25
A Module 2, phase
2
0 21 27
A Module 2, phase
3
0 23 29
B Module 1, phase
1
0 20 25
B Module 1, phase
2
0 21 27
B Module 1, phase
3
0 23 29
B Module 2, phase
1
0 21 27
B Module 2, phase
2
0 23 30
B Module 2, phase
3
0 22 28
Table 5-51 (page 5-46) lists the threshold values for Oracle Exadata Database
Machine X3-8 Full Rack using a single-phase, high-voltage 22 kVA PDU.
Table 5-51 Threshold Values for Oracle Exadata Database Machine X3-8 Full
Rack with Single-phase, High-voltage 22 kVA PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 22 28
A and B Module 1, phase
2
0 24 30
A and B Module 1, phase
3
0 22 28
Table 5-52 (page 5-47) lists the threshold values for Oracle Exadata Database
Machine X3-8 Full Rack using a three-phase, high-voltage 24 kVA PDU.
Chapter 5
Configuring the Power Distribution Units