Table 1-8 (Cont.) Environmental Requirements for Oracle Exadata Database
Machine X3-8 Full Rack with Exadata Storage Server X3-2 Servers
Environmental Component Oracle Exadata Database Machine X3-8
Full Rack with Exadata Storage Server
X3-2 Servers
Network drops
See Also: "Network Connection and IP
Address Requirements for Oracle Exadata
Database Machine (page 1-47)"
Minimum of 5 network drops
External connectivity
See Also: "Network Connection and IP
Address Requirements for Oracle Exadata
Database Machine (page 1-47)"
16 x 1 GbE Ethernet ports
16 x 10 GbE Ethernet SFP+ ports
12 InfiniBand ports
1.1.10 General Environmental Requirements for Oracle Exadata
Database Machine X2-2
The environmental requirements for Oracle Exadata Database Machine X2-2 depend
on the size of the system. Table 1-9 (page 1-17) shows the general environmental
requirements for Oracle Exadata Database Machine X2-2. The other sections in this
chapter provide detailed information.
Table 1-9 Environmental Requirements for Oracle Exadata Database Machine
X2-2
Environmental
Component
Oracle Exadata
Database Machine
X2-2 Full Rack
Oracle Exadata
Database Machine
X2-2 Half Rack
Oracle Exadata
Database Machine
X2-2 Quarter Rack
Weight
See Also: "Flooring
Requirements
(page 1-34)"
966.6 kg (2131 lbs) 602.8 kg (1329 lbs) 409.1kg (902 lbs)
Acoustic levels 89 db(A) 86 db(A) 83 db(A)
Power
See Also: "Electrical
Power Requirements
(page 1-34)"
Maximum: 14.0 kW
(14.3 kVA)
Typical: 9.8 kW (10.0
kVA) (varies based on
application load)
Maximum: 7.2 kW
(7.3 kVA)
Typical: 5.1 kW (5.2
kVA) (varies based on
application load)
Maximum: 3.6 kW
(3.7 kVA)
Typical: 2.7 kW
(2.75kVA) (varies
based on application
load)
Cooling
See Also:
"Temperature and
Humidity
Requirements
(page 1-44)", and
"Ventilation and
Cooling Requirements
(page 1-45)"
Maximum: 47,800
BTU/hour (50,400 kJ/
hour)
Typical: 33,400 BTU/
hour (35,300 kJ/hour)
Maximum: 26,400
BTU/hour (25,950 kJ/
hour)
Typical: 17,400 BTU/
hour (35,300 kJ/hour)
Maximum: 12,300
BTU/hour (13,000 kJ/
hour)
Typical: 9,200 BTU/
hour (9,700 kJ/hour)
Chapter 1
General Environmental Requirements
1-17