5.3.1.6 PDU Thresholds for Oracle Exadata Database Machine X4-8 and Later
This section contains the PDU thresholds for Oracle Exadata Database Machine
Eight-Socket systems for X4-8 and later.
Oracle Exadata Configuration Assistant (OECA) is the only source for PDU thresholds
for Oracle Exadata Database Machine X4-8 and later systems. OECA is available on
Oracle Technology Network at http://www.oracle.com/technetwork/database/exadata/
oeca-download-2817713.html
If for some reason you are unable to utilize OECA, contact Oracle Support.
5.3.1.7 PDU Thresholds for Oracle Exadata Database Machine X3-8 Full Rack
This section contains the PDU thresholds for Oracle Exadata Database Machine X3-8
Full Rack.
Table 5-49 (page 5-45) Threshold Values for Oracle Exadata Database Machine
X3-8 Full Rack with Single-phase, Low-voltage 22 kVA PDU
Table 5-50 (page 5-46) Threshold Values for Oracle Exadata Database Machine
X3-8 Full Rack with Three-phase, Low-voltage 24 kVA PDU
Table 5-51 (page 5-46) Threshold Values for Oracle Exadata Database Machine
X3-8 Full Rack with Single-phase, High-voltage 22 kVA PDU
Table 5-52 (page 5-47) Threshold Values for Oracle Exadata Database Machine
X3-8 Full Rack with Three-phase, High-voltage 24 kVA PDU
Table 5-49 (page 5-45) lists the threshold values for Oracle Exadata Database
Machine X3-8 Full Rack using a single-phase, low-voltage 22 kVA PDU.
Table 5-49 Threshold Values for Oracle Exadata Database Machine X3-8 Full
Rack with Single-phase, Low-voltage 22 kVA PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 25 31
A Module 1, phase
2
0 26 33
A Module 1, phase
3
0 24 30
B Module 1, phase
1
0 24 30
B Module 1, phase
2
0 26 33
B Module 1, phase
3
0 25 31
Table 5-50 (page 5-46) lists the threshold values for Oracle Exadata Database
Machine X3-8 Full Rack using a three-phase, low-voltage 24 kVA PDU.
Chapter 5
Configuring the Power Distribution Units
5-45