Table 5-35 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, High-voltage
PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 9 12
A Module 1, phase
2
0 5 7
A Module 1, phase
3
0 0 0
B Module 1, phase
1
0 0 0
B Module 1, phase
2
0 5 7
B Module 1, phase
3
0 9 12
Table 5-36 (page 5-38) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a three-phase, high-voltage PDU.
Table 5-36 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, High-voltage
PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 9 12
A and B Module 1, phase
2
0 3 4
A and B Module 1, phase
3
0 4 5
5.3.1.5 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers)
This section contains the PDU thresholds for Oracle Exadata Database Machine X2-2
(with X4170 and X4275 servers).
Chapter 5
Configuring the Power Distribution Units