• Table 5-36 (page 5-38) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase,
High-voltage PDU
Table 5-33 (page 5-37) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a single-phase, low-voltage PDU.
Table 5-33 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, Low-voltage
PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 10 13
A Module 1, phase
2
0 6 8
A Module 1, phase
3
0 0 0
B Module 1, phase
1
0 0 0
B Module 1, phase
2
0 6 8
B Module 1, phase
3
0 10 13
Table 5-34 (page 5-37) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a three-phase, low-voltage PDU.
Table 5-34 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, Low-voltage
PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 12 15
A and B Module 1, phase
2
0 11 14
A and B Module 1, phase
3
0 5 7
Table 5-35 (page 5-38) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a single-phase, high-voltage PDU.
Chapter 5
Configuring the Power Distribution Units
5-37