Table 5-67 Threshold Values for Oracle Exadata Storage Expansion Quarter
Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Single-
phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 9 12
A Module 1, phase
2
0 5 7
A Module 1, phase
3
0 0 0
B Module 1, phase
1
0 0 0
B Module 1, phase
2
0 5 7
B Module 1, phase
3
0 9 12
Table 5-68 (page 5-55) lists the threshold values for Oracle Exadata Storage
Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2
Servers using a three-phase, high-voltage PDU.
Table 5-68 Threshold Values for Oracle Exadata Storage Expansion Quarter
Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Three-
phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 9 12
A and B Module 1, phase
2
0 3 4
A and B Module 1, phase
3
0 4 5
5.4 Checking Exadata Storage Servers
The following procedure describes how to check Exadata Storage Servers:
Chapter 5
Checking Exadata Storage Servers
5-55