• Table 5-67 (page 5-55) Threshold Values for Oracle Exadata Storage Expansion
Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Single-phase, High-voltage PDU
• Table 5-68 (page 5-55) Threshold Values for Oracle Exadata Storage Expansion
Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Three-phase, High-voltage PDU
Table 5-65 (page 5-54) lists the threshold values for Oracle Exadata Storage
Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2
Servers using a single-phase, low-voltage PDU.
Table 5-65 Threshold Values for Oracle Exadata Storage Expansion Quarter
Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Single-
phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 10 13
A Module 1, phase
2
0 6 8
A Module 1, phase
3
0 0 0
B Module 1, phase
1
0 0 0
B Module 1, phase
2
0 6 8
B Module 1, phase
3
0 10 13
Table 5-66 (page 5-54) lists the threshold values for Oracle Exadata Storage
Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2
Servers using a three-phase, low-voltage PDU.
Table 5-66 Threshold Values for Oracle Exadata Storage Expansion Quarter
Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Three-
phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 12 15
A and B Module 1, phase
2
0 11 14
A and B Module 1, phase
3
0 5 7
Table 5-67 (page 5-55) lists the threshold values for Oracle Exadata Storage
Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2
Servers using a single-phase, high-voltage PDU.
Chapter 5
Configuring the Power Distribution Units