Table 5-46 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Quarter Rack with Three-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 13 17
A and B Module 1, phase
2
0 12 15
A and B Module 1, phase
3
0 5 7
Table 5-47 (page 5-44) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a single-phase, high-voltage PDU.
Table 5-47 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Quarter Rack with Single-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 11 14
A Module 1, phase
2
0 5 7
A Module 1, phase
3
0 0 0
B Module 1, phase
1
0 0 0
B Module 1, phase
2
0 5 7
B Module 1, phase
3
0 11 14
Table 5-48 (page 5-44) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a three-phase, high-voltage PDU.
Table 5-48 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Quarter Rack with Three-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 11 14
A and B Module 1, phase
2
0 2 3
A and B Module 1, phase
3
0 3 4
Chapter 5
Configuring the Power Distribution Units