Table 5-53 Threshold Values for Oracle Exadata Database Machine X2-8 Full
Rack with Single-phase, Low-voltage 22 kVA PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 36 37
A Module 1, phase
2
0 35 37
A Module 1, phase
3
0 35 37
B Module 1, phase
1
0 35 37
B Module 1, phase
2
0 35 37
B Module 1, phase
3
0 36 37
Table 5-54 (page 5-48) lists the threshold values for Oracle Exadata Database
Machine X2-8 Full Rack using a three-phase, low-voltage 24 kVA PDU.
Table 5-54 Threshold Values for Oracle Exadata Database Machine X2-8 Full
Rack with Three-phase, Low-voltage 24 kVA PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 32 40
A and B Module 1, phase
2
0 34 43
A and B Module 1, phase
3
0 33 42
Table 5-55 (page 5-48) lists the threshold values for Oracle Exadata Database
Machine X2-8 Full Rack using a single-phase, high-voltage 22 kVA PDU.
Table 5-55 Threshold Values for Oracle Exadata Database Machine X2-8 Full
Rack with Single-phase, High-voltage 22 kVA PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 26 32
A and B Module 1, phase
2
0 25 32
A and B Module 1, phase
3
0 26 32
Chapter 5
Configuring the Power Distribution Units
5-48

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle EXADATA X6-2 and is the answer not in the manual?

Oracle EXADATA X6-2 Specifications

General IconGeneral
BrandOracle
ModelEXADATA X6-2
CategoryServer
LanguageEnglish

Related product manuals