Table 1-3 Environmental Requirements for Oracle Exadata Database Machine
X4-2
Environmental
Component
Oracle Exadata
Database
Machine X4-2
Full Rack
Oracle Exadata
Database
Machine X4-2
Half Rack
Oracle Exadata
Database
Machine X4-2
Quarter Rack
Oracle Exadata
Database
Machine X4-2
Eighth Rack
Weight
See Also:
"Flooring
Requirements
(page 1-34)"
852.8 kg (1880
lbs)
525.3 kg (1158
lbs)
365.6 kg (806
lbs)
365.6 kg (806
lbs)
Acoustic levels 93 db(A) 89 db(A) 85 db(A) 85 db(A)
Power
See Also:
"Electrical Power
Requirements
(page 1-34)"
High
performance
drives
Maximum:
12.4 kVA
Typical: 8.7
kVA (varies
based on
application
load)
High
capacity
drives
Maximum:
11.4 kVA
Typical: 8.1
kVA (varies
based on
application
load)
High
performance
drives
Maximum:
6.8 kVA
Typical: 4.8
kVA (varies
based on
application
load)
High
capacity
drives
Maximum:
6.3 kVA
Typical: 4.4
kVA (varies
based on
application
load)
High
performance
drives
Maximum:
3.4 kVA
Typical: 2.5
kVA (varies
based on
application
load)
High
capacity
drives
Maximum:
3.2 kVA
Typical: 2.3
kVA (varies
based on
application
load)
High
performance
drives
Maximum:
3.1 kVA
Typical: 2.2
kVA (varies
based on
application
load)
High
capacity
drives
Maximum:
2.9 kVA
Typical: 2.1
kVA (varies
based on
application
load)
Chapter 1
General Environmental Requirements
1-6