Table 1-13 (Cont.) Environmental Requirements for Oracle Exadata Storage
Expansion Rack X3-2
Environmental
Component
Oracle Exadata
Storage Expansion
X3-2 Full Rack
Oracle Exadata
Storage Expansion
X3-2 Half Rack
Oracle Exadata
Storage Expansion
X3-2 Quarter Rack
Power • High performance
drives
Maximum: 10.2
kVA
Typical: 7.1 kVA
(varies based on
application load)
• High capacity
drives
Maximum: 8.9
kVA
Typical: 6.2 kVA
(varies based on
application load)
• High performance
drives
Maximum: 5.7
kVA
Typical: 4.1 kVA
(varies based on
application load)
• High capacity
drives
Maximum: 5.1
kVA
Typical: 3.6 kVA
(varies based on
application load)
• High performance
drives
Maximum: 2.9
kVA
Typical: 2.0 kVA
(varies based on
application load)
• High capacity
drives
Maximum: 2.6
kVA
Typical: 1.9 kVA
(varies based on
application load)
Cooling • High performance
drives
Maximum: 34,100
BTU/hour (36,000
kJ/hour)
Typical: 23,900
BTU/hour (25,200
kJ/hour)
• High capacity
drives
Maximum: 29,700
BTU/hour (31,300
kJ/hour)
Typical: 20,800
BTU/hour (21,950
kJ/hour)
• High performance
drives
Maximum: 19,100
BTU/hour (20,150
kJ/hour)
Typical: 13,650
BTU/hour (14,400
kJ/hour)
• High capacity
drives
Maximum: 17,100
BTU/hour (18,000
kJ/hour)
Typical: 11,950
BTU/hour (12,600
kJ/hour)
• High performance
drives
Maximum: 9,500
BTU/hour (10,000
kJ/hour)
Typical: 6,700
BTU/hour (7,000
kJ/hour)
• High capacity
drives
Maximum: 8,500
BTU/hour (9,000
kJ/hour)
Typical: 6,150
BTU/hour (6,500
kJ/hour)
Air flow front-to-back
(subject to actual data
center environment)
• High performance
drives
Maximum:
Approximately
1,600 CFM
Typical:
Approximately
1,100 CFM
• High capacity
drives
Maximum:
Approximately
1,375 CFM
Typical:
Approximately
960 CFM
• High performance
drives
Maximum:
Approximately
900 CFM
Typical:
Approximately
650 CFM
• High capacity
drives
Maximum:
Approximately
790 CFM
Typical:
Approximately
550 CFM
• High performance
drives
Maximum:
Approximately
440 CFM
Typical:
Approximately
310 CFM
• High capacity
drives
Maximum:
Approximately
400 CFM
Typical:
Approximately
285 CFM
Chapter 1
General Environmental Requirements
1-24

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle EXADATA X6-2 and is the answer not in the manual?

Oracle EXADATA X6-2 Specifications

General IconGeneral
BrandOracle
ModelEXADATA X6-2
CategoryServer
LanguageEnglish

Related product manuals