Table 1-16 Environmental Requirements for X6-2 Single Servers
Environmental
Component
Exadata Storage
Server X6-2 -
Extreme Flash
Exadata Storage
Server X6-2 - High
Capacity
Database Server
X6-2
Weight 28.1 kg (62 lbs) 33.1 kg (73 lbs) 20.4 kg (45 lbs)
Acoustic levels 78 db(A) 78 db(A) 78 db(A)
Power Maximum: 0.6 kVA
Typical: 0.4 kVA
(varies based on
application load)
Maximum: 0.6 kVA
Typical: 0.4 kVA
(varies based on
application load)
Maximum: 0.665 kW
(0.678 kVA)
Typical: 0.466 kW
(0.475 kVA) (varies
based on application
load)
Cooling Maximum: 1,866 BTU/
hour (1,969 kJ/hour)
Typical: 1,307 BTU/
hour (1,378 kJ/hour)
Maximum: 2,006 BTU/
hour (2,117 kJ/hour)
Typical: 1,404 BTU/
hour (1,482 kJ/hour)
Maximum: 2,269 BTU/
hour (2,394 kJ/hour)
Typical: 1,588 BTU/
hour (1,676 kJ/hour
Air flow front-to-back
(subject to actual data
center environment)
Maximum:
Approximately 86
CFM
Typical:
Approximately 60
CFM
Maximum:
Approximately 93
CFM
Typical:
Approximately 65
CFM
Maximum:
Approximately 105
CFM
Typical:
Approximately 74
CFM
Table 1-17 Environmental Requirements for X5-2 Single Servers
Environmental
Component
Exadata Storage
Server X5-2 -
Extreme Flash
Exadata Storage
Server X5-2 - High
Capacity
Database Server
X5-2
Weight 28.1 kg (62 lbs) 33.1 kg (73 lbs) 20.4 kg (45 lbs)
Acoustic levels 78 db(A) 78 db(A) 78 db(A)
Power Maximum: 0.6 kVA
Typical: 0.4 kVA
(varies based on
application load)
Maximum: 0.6 kVA
Typical: 0.4 kVA
(varies based on
application load)
Maximum: 0.7 kVA
Typical: 0.5 kVA
(varies based on
application load)
Cooling Maximum: 2,037 BTU/
hour (2,149 kJ/hour)
Typical: 1,426 BTU/
hour (1,504 kJ/hour)
Maximum: 2,000 BTU/
hour (2,109 kJ/hour)
Typical: 1,400 BTU/
hour (1,477 kJ/hour)
Maximum: 2,481 BTU/
hour (2,617 kJ/hour)
Typical: 1,736 BTU/
hour (1,832 kJ/hour
Air flow front-to-back
(subject to actual data
center environment)
Maximum:
Approximately 94
CFM
Typical:
Approximately 66
CFM
Maximum:
Approximately 93
CFM
Typical:
Approximately 65
CFM
Maximum:
Approximately 115
CFM
Typical:
Approximately 80
CFM
Chapter 1
General Environmental Requirements
1-27