12.2.4 Handling of Master Memories Created with Different Models
PLC that created master memory
Ry type
Tr type
C14
C30
C60
C14
C30
C60
Installed
PLC
Ry type
C14
A
E25
E25
E25
C30
A A A E25 E25 E25
C60
A
A
A
E25
E25
E25
Tr type
C14
E25 E25 E25 A
C30
E25
E25
E25
A
A
A
C60
E25 E25 E25 A A A
A: Can be installed and operated.
: Can be installed depending on the program capacity.
E25: Master memory model unmatch error
Note1) If the E25 occurs, the mode will not be the RUN.
Also, the transfer operation from the master memory to the internal memory of the controller will
not be executed.
The transfer operation from the internal memory of the controller to the master memory can be
executed even if the E25 occurs.
Note2) If the version of the Ry type is older than Ver2.0, the E26 (Users ROM error) is detected not the
E25.
Note3) Use the tool software to execute the program conversion between different models.