DOC-0017-04-EN: AC20 Series - Hardware Installation Manual
DOC-0017-04-EN-A 22.03.2023 13 (154)
General Power Stack Features:
Switching Frequency:
Default:
- Frames 2 6: 4kHz
- Frame 7: 3kHz
- Frames 8 10: 2kHz
Maximum:
- Frames 2 6 (1.5 37kW): 10kHz
- Frame 6 (45kW): 6kHz
- Frame 7: 8kHz
- Frames 8 10: 4kHz
Linear derating of output current will apply above the default switching
frequency (varies by power rating. Refer to Chapter 13: Technical
Information for values).
Output Frequency:
- Maximum = Switching Frequency ÷ 8
PMAC Motors:
- Maximum = Switching Frequency ÷ 6
Note: Output frequency is limited to a maximum frequency of 590Hz
due to export rules.
Duty Rating:
Power Stack Protection Features:
Trip Conditions:
Overcurrent: 220% Rated Output Current
Motor Stall
Overvoltage / Undervoltage:
- 230V products = 420Vdc / 220Vdc
- 400V products = 840Vdc / 420Vdc
Heatsink Overtemperature
Motor Thermistor Overtemperature
Three Phase OK (Missing Line Phase Detection):
- 3ø 230V products: Frames 3 – 5 only
- 3ø 400V products: Frames 4 10 only
Current Limit:
Overload Rating:
User Terminals:
Line Input:
Motor Output:
Brake Output:
PE:
General Control Features:
Motor Control Modes:
- V/F Control (V/Hz)
- Sensorless Vector Control
- Closed Loop Vector Control (with Encoder Feedback Option
Board)
PMAC Motors:
- Sensorless Vector Control
Voltage Boost for V/F
Control:
0-25%