EasyManua.ls Logo

Parker AC20 Series - Page 29

Parker AC20 Series
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DOC-0017-04-EN: AC20 Series - Hardware Installation Manual
DOC-0017-04-EN-A 22.03.2023 29 (154)
Terminal Block Guards (Frames 6 10)
The Frame 6 10 products have an additional protective guard on the power terminal blocks that must be
temporarily removed out of the way when wiring the drive.
These guards must be refitted once the power wiring is installed.
Frames 6 & 7:
The clear terminal covers unclip and pull away from the terminal block to expose the power terminal
connections:
Frames 8 10:
The clear terminal covers slide upwards from the terminal block to expose the power terminal connections:
Terminal Block Wire Range (Europe)
Wire sizes for Europe should be chosen with respect to the inverter operating conditions, in addition to local
National Electrical Safety Installation Requirements. Local wiring regulations always take precedence.
230V Products:
Frame
Size
AC Line Input
Terminals
(L1/L, L2/N,
L3)
DC Link /
Brake Output
Terminals
(DC+, DC-,
DBR)
Motor Output
Terminals
(U, V, W)
Earth
Terminal
(PE)
Chassis Earth
Clamp
(PE)
2
1.5 4.0
M4 Fork Crimp
3
4.0 10.0
M4 Fork Crimp
4
0.5 – 10.0
M4 Fork Crimp
5
0.5 35.0
M4 Fork Crimp
All cable size ranges specified in mm
2
400V Products:
Frame
Size
AC Line Input
Terminals
(L1/L, L2/N,
L3)
DC Link /
Brake Output
Terminals
(DC+, DC-,
DBR)
Motor Output
Terminals
(U, V, W)
Earth
Terminal
(PE)
Chassis Earth
Clamp
(PE)
2
1.5 4.0
M4 Fork Crimp
3
4.010.0
M4 Fork Crimp
4
0.5 – 10.0
M4 Fork Crimp
5
0.5 35.0
M5 Fork Crimp
All cable size ranges specified in mm