Bulletin 100-50-9.1 – Page 101
11.5  SENSOR CONFIGURATION
The S3C supports Sporlan 10K thermistors and 0.5 to 
4.5V ratiometric pressure transducers by default. There 
are several additional options that are available in the 
controller. The following steps can be followed to change 
the defaults.
11.5.1  TEMPERATURE SENSORS
1.  From the default display, press the  button. The 
display will show   .
2.  Use the ▲▼ buttons to enter the administrator 
password and press SET.
3.  The display will show ; press SET.
4.  Press the ▲ button to scroll to the e(sensor 
configuration menu); press SET.
5.  Press the ▲ button to scroll to  (thermistor type); 
press SET.
6.  Press the ▼ button to scroll thru the options 1 (10k),  
3 (3k), 2 (2k); press SET.
7.  Press ESC button three times to return to default 
display.
11.5.2 PRESSURE TRANSDUCERS
11.5.2.1 PRESSURE TRANSDUCER TYPE
1.  From the default display, press the  button. The 
display will show   .
2.  Use the ▲▼ buttons to enter the administrator 
password and press SET.
3.  The display will show ; press SET.
4.  Press the ▲ button to scroll to the e(sensor 
configuration menu); press SET.
5.  Press the ▲ button to scroll to (pressure transducer 
type); press SET.
6.  Press the ▼ button to scroll thru the options 
gug(gauge) or (absolute); press SET.
7.  Press ESC button three times to return to default 
display.
11.5.2.2 PRESSURE TRANSDUCER RANGE
1.  From the default display, press the  button. The 
display will show   .
2.  Use the ▲▼ buttons to enter the administrator 
password and press SET.
3.  The display will show ; press SET.
4.  Press the ▲ button to scroll to the e(sensor 
configuration menu); press SET.
5.  Press the ▲ button to scroll to g (pressure 
transducer range); press SET.
6.  Press the ▲▼ button to scroll thru the options; then 
press SET.
7.  Press the ESC button three times to return to default 
display.
11.5.2.3 CUSTOM PRESSURE TRANSDUCER
A custom transducer range may be configured in the S3C. 
The transducer must be a 0.5 to 4.5V ratiometric with 
5V supply. The custom configuration has a range of 50 to 
2000psi.
1.  From the default display, press the  button. The 
display will show   .
2.  Use the ▲▼ buttons to enter the administrator 
password and press SET.
3.  The display will show ; press SET.
4.  Press the ▲ button to scroll to the e(sensor 
configuration menu); press SET.
5.  Press the ▲ button to scroll to g; press SET.
6.  Press the ▲ button to scroll to U(custom); press 
SET. This will enable the custom parameters.
7.  With the display at g, press the ▲ button to scroll to 
(custom pressure transducer range); press SET.
8.  Use the ▲▼ buttons to scroll to the desired pressure 
range; press SET. For example; to support a 200psi 
transducer, set  to 2.
9.  Press the ESC button three times to return to default 
display.
11.5.2.4  MULTIPLE PRESSURE TRANS
DUCERS FOR MULTICOIL CASES
For multi-coil cases, one pressure transducer may be used 
per case or per evaporator. For a single transducer design, 
the S3C will use the common suction pressure across all 
evaporators to control superheat. If a pressure transducer 
is used per evaporator, then the S3C will control superheat 
based on the pressure of each evaporator. See Section 6 for 
recommended wiring and piping diagrams per application.
11.6  SENSOR CALIBRATION OFFSET
The temperature, pressure and relative humidity sensors 
may be calibrated with an offset that is configurable in the 
S3C.
1.  From the default display, press the  button. The 
display will show   .
2.  Use the ▲▼ buttons to enter the administrator 
password and press SET.
3.  The display will show ; press SET.
Display Description
u
Custom Transducer (see below for configuration)
652
652 psi
5
500 psi
3
300 psi
15
150 psi