Page 36 – Bulletin 100-50-9.1
6.5  REMOTE SINGLE EVAPORATOR – CONFIGURATION E
The S3C case controller is capable of controlling and monitoring single temperature, single evaporator refrigerated fixtures 
installed as a line-up. The case shown in the diagram below is the lead case of the line-up. In this scenario, one S3C case 
controller is required. The S3C case controller will control all case functions as well as take all the desired sensor inputs.
The typical control method:
Without mechanical EPR: TEV will control superheat and liquid line solenoid will control case temperature using cut-in/
cut-out method.
With mechanical EPR: TEV will control superheat and the EPR will control case temperature.
The liquid line solenoid (LLS) may be installed as one-per-case or one-per-line-up if no EPR is used or if an EPR per line-
up is used. Case numbers 2, 3, 4,...n will require their own S3C case controller as well.
To configure the S3C control package for configuration E 
shown above, follow these directions:
If the controller has not been factory set, then upon initial 
start-up, the controller will be in set-up mode and the 
screen will display  (for self-contained case).
1.  Press the SET button, then use ▲▼ buttons to scroll 
to o; press SET. is will congure the controller to 
support a remote case.
2.  Press the SET button when  (Rack Identier) 
is displayed. Use the ▲▼ buttons to congure the 4 
character Rack Identier. Note: Push ▲ button for 
numeric, ▼ for alpha characters. When satised 
with each digit, press the SET button to go to the next 
digit. Pressing SET multiple times will move to the next 
parameter.
3.  Press the SET button when ud (Line-up Identier) 
is displayed. Use the ▲▼ buttons to congure the 4 
character Line-up Identier. Note: Push 
▲
 button for 
numeric, 
▼
 for alpha characters. When satised 
with each digit, press the SET button to go to the next 
digit. Pressing SET multiple times will move to the next 
parameter.
4.  Press the SET button when d (Case Identier) 
is displayed. Use the ▲▼ buttons to congure the 4 
character Case Identier. Note: Push ▲ button for 
numeric, ▼ for alpha characters. When satised 
with each digit, press the SET button to go to the next 
digit. Pressing SET multiple times will move to the next 
parameter.
5.  Press the SET button when  (Application Type) is 
displayed. Use the ▲ button and scroll to  (Single 
Temperature Case); press SET.
6.  Press the SET button when  (Local Stepper Valve 
Conguration) is displayed. Use the ▲ button to scroll 
to oe (None for ermostatic Expansion Valve); press 
SET.
Compressor Suction
CASE
From CASE #n
Liquid
Liquid Line
Solenoid
REMOTE SINGLE EVAPORATOR – CONFIGURATION E