Bulletin 100-50-9.1 – Page 121
RED denotes required control conguration to enable alarm and/or control response.
Alarm Description Cause Control Response
Self
Clearing


EEV Open Load/SFV Open Load
EEV/SFV configured for 1 evaporator.
EEV not connected, miswired or open
winding/connection.
Yes
1
Left coil EEV Open Load
EEV Configured for 2 or more
evaporators. Left evaporator EEV
assigned to S3C Case Control not
connected, miswired or open winding/
connection.
Yes
2
Center coil EEV Open Load
EEV Configured for 3 evaporators.
Center evaporator EEV assigned to S3C
Valve Module not connected, miswired
or open winding/connection.
Yes
3
Right coil EEV Open Load
EEV Configured for 2 or 3 evaporators.
Right evaporator EEV assigned to S3C
Valve Module not connected, miswired
or open winding/connection.
Yes

Multiple EEPRs configured for line-up
EEPR assigned to more than 1 control
in line-up
Yes
doo
Door Open
Door opening detection input to control
configured (Walk-In only).
Door Open time exceeds user selected
Door Open alarm delay time.
Yes

Building Automation System
communication fault
S3C Case Control configured for
BAS present. BAS Network settings
incorrect, Communication wiring
incorrect.
Yes
M
Valve Module (VM) communication
fault (Device Expansion Network
(DEN))
S3C Case Control configured for
presence of 1 or more Valve Modules.
DEN wiring incorrect. Failed VM. VM
dip switches configured for EEV when
EEPR selected or when 2 evaporators
selected.
Yes

Case Network communication fault.
S3C Case Control configured for
presence of 2 or more controls in line-
up. Case Network settings incorrect,
Communication wiring incorrect. Failed
S3C Control in line-up.
Yes
18.3 SENSOR ALARMS
RED denotes required control conguration to enable alarm and/or control response.
Alarm Description Cause Control Response
Self
Clearing
o

Alternating o  at default
screen when no Discharge Air (DA)
sensor(s) detected
Discharge Air sensor(s) not
connected, miswired or shorted.
EEPR Temperature control selected.
1. Single case in line-up with single
evaporator. One DA sensor
connected to S3C Case Controller:
EEPR moves to calculated “fault”
position.
2. Multiple cases in line-up and /
or multiple evaporators with DA
sensors: Average temperature value
from remaining available sensors is
used for control.
Yes

Circuit Coil Outlet temperature sensor
fault
The coil outlet temperature sensor for
the circuit is not connected, miswired,
or shorted.
1
No Suction Pressure Transducer
detected on Left Evaporator (S3C
Case Control pressure input).
2 or 3 Evaporators with multiple
suction pressure transducers
installed in case.
Superheat Control using EEV
selected. Number of evaporators in
case greater than 1. Sensor must be
detected on initial power up to enable
alarm. Pressure Transducer(s) not
connected, miswired or faulty.
Superheat Control selected.
1. EEV closes to prevent possible flood
back.
2. Pressure Sharing Enabled: Average
pressure value from remaining
available pressure transducers is
used for superheat calculation.
Yes