Bulletin 100-50-9.1 – Page 125
For Coil 1:
1. From the default display, press the button to 
then press SET.
2. Press the button and scroll to d1.
3. Press SET button to show current discharge air value.
4. Press ESC button three times to return to default
display.
For Coil 2:
1. From the default display, press the button to 2
then press SET.
2. Press the button and scroll to d.
3. Press SET button to show current discharge air value.
4. Press ESC button three times to return to default
display.
For Coil 3:
1. From the default display, press the button to 3
then press SET.
2. Press the button and scroll to d.
3. Press the SET button to show current superheat value.
4. Press the ESC button three times to return to default
display.
19.4 VIEW SUPERHEAT
19.4.1 SINGLE COIL CASE
1. From the default display, press the button to 
then press SET.
2. Press the button and scroll to h.
3. Press SET button to show current superheat value.
4. Press ESC button three times to return to default
display (discharge air).
19.4.2 MULTICOIL CASE
For Coil 1:
1. From the default display, press the button to 
then press SET.
2. Press the button and scroll to h1.
3. Press SET button to show current superheat value.
4. Press ESC button three times to return to default
display (discharge air).
For Coil 2:
1. From the default display, press the button to 2
then press SET.
2. Press the button and scroll to h.
3. Press SET button to show current superheat value.
4. Press ESC button three times to return to default
display (discharge air).
For Coil 3:
1. From the default display, press the button to 3
then press SET.
2. Press the button and scroll to h.
3. Press SET button to show current superheat value.
4. Press ESC button three times to return to default
display (discharge air).
19.5 VIEW SUCTION PRESSURE
1. From the default display, press the button to 
then press SET.
2. Press the button and scroll to U.
3. Press SET button to show suction pressure value.
4. Press ESC button three times to return to default
display (discharge air).
19.6 VIEW COIL OUTLET TEMPERATURE
19.6.1 SINGLE COIL CASE
1. From the default display, press the button to e
then press SET.
2. Press the button and scroll to oU.
3. Press SET button to show evaporator coil outlet
temperature.
4. Press ESC button three times to return to default
display.
19.6.2 MULTICOIL CASE
For Coil 1:
1. From the default display, press the button to 
then press SET.
2. Press the button and scroll to o1.
3. Press SET button to show evaporator coil outlet
temperature.
4. Press ESC button three times to return to default
display.
For Coil 2:
1. From the default display, press the button to 2
then press SET.
2. Press the button and scroll to oU.
3. Press SET button to show evaporator coil outlet
temperature.
4. Press ESC button three times to return to default
display.
For Coil 3:
1. From the default display, press the button to 3
then press SET.
2. Press the button and scroll to oU.
3. Press SET button to show evaporator coil outlet
temperature.
4. Press ESC button three times to return to default
display.
19.7 VIEW EEV POSITION
19.7.1 SINGLE COIL CASE
1. From the default display, press the button to 
then press SET.
2. Press the button and scroll to .

Table of Contents

Other manuals for Parker Sporlan S3C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker Sporlan S3C and is the answer not in the manual?

Parker Sporlan S3C Specifications

General IconGeneral
BrandParker
ModelSporlan S3C
CategoryController
LanguageEnglish

Related product manuals