Page 98 – Bulletin 100-50-9.1
11.3 CASE LEVEL CONFIGURATION
The case level menu can be used to view and change case
parameters. It may be used for troubleshooting or updating
parameters.
To access Case Level Menus:
1. From the default display, press the button. e
display will show   .
2. Use the ▲▼ buttons to enter the administrator
password and press SET.
3. e display will show ; press SET.
4. Use the ▲▼ buttons to select the desired parameter, see
Table 8 below.
5. Press the SET button to enter and change the
parameter.
6. After adjusting the parameter, press the SET button to
commit the change.
11.4 BASIC OPERATIONAL CONFIGURATION
The basic menu presents key case parameters that may be
changed. If entering this menu thru the Administration
level password, changes will be permanent. Use caution
when changing parameters from the original OEM settings.
To access Basic Parameter Menu:
7. From the default display, press the button. e
display will show   .
8. Use the ▲▼ buttons to enter the administrator
password and press SET.
9. e display will show ; press SET.
10. Press the button to scroll to the basic menu ;
press SET.
11. Use the ▲▼ buttons to select the desired parameter.
12. Press the SET button to enter and change the
parameter.
TABLE 6  TOP LEVEL MENUS
Display Meaning Description Hide Condition

Case Configuration Allows configuration of case level parameters
e
Line-up Configuration Allows viewing of line-up level process values (1)
3
Evaporator 3
Configuration
Allows configuration of evaporator level sensors offsets for evaporator 3 (2)
2
Evaporator 2
Configuration
Allows configuration of evaporator level sensors offsets for evaporator 2 (3)
TABLE 7  HIDE CONDITIONS FOR TOP LEVEL MENU ITEMS
Number Hide Condition
1 Case type is self-contained
2
e Number of evaporators is configured to < 3
3
e Number of evaporators is configured to 1
TABLE 8  CASE CONFIGURATION MENUS
Display Meaning Description

Process values Allows viewing of operational and sensed values

Basic operational configuration Configuration of basic operational settings

Valve configuration Configuration of attached valves

Sensor configuration Configures type, range, offset and use of sensors

User alarm configuration Configures user alarm thresholds and delays
d
Display (DM) configuration Configures passwords, display actions and units

Lighting control configuration Configures lighting schedule and occupancy sensor action
def
Defrost configuration Configures defrost type and settings
f
Evaporator fan control configuration Configures evaporator fan settings and alarms

Anti-sweat heater control configuration Configures anti-sweat heater control
d
Case controller indentifier configuration Indentifies case location based on rack and line-up ID
e
Network configuration Configures network for BAS and peer - peer
de
Set time and date Used for setting internal real time clock (RTC)