Page 126 – Bulletin 100-50-9.1
3. Press SET button to show EEV position.
4. Press ESC button three times to return to default
display.
19.7.2 MULTICOIL CASE
For Coil 1:
1. From the default display, press the button to 
then press SET.
2. Press the button and scroll to 1.
3. Press SET button to show EEV position.
4. Press ESC button three times to return to default
display.
For Coil 2:
1. From the default display, press the button to 2
then press SET.
2. Press the button and scroll to .
3. Press SET button to show EEV position.
4. Press ESC button three times to return to default
display.
For Coil 3:
1. From the default display, press the button to 3
then press SET.
2. Press the button and scroll to .
3. Press SET button to show EEV position.
4. Press ESC button three times to return to default
display.
19.8 VIEW EEPR POSITION
19.8.1 LINEUP EEPR
The EEPR position may be viewed from any Display Module
(DM) on the line-up.
1. From the default display, press the button to show
N then press SET.
2. Press the button and scroll to .
3. Press SET button to show EEPR position.
4. Press ESC button three times to return to default
display (discharge air).
19.8.2 CASE EEPR
Each case EEPR position can only be viewed thru the
corresponding case Display Module (DM).
1. From the default display, press the button to show
 then press SET.
2. Press the button and scroll to .
19.9 ADJUST SUPERHEAT SETPOINT
1. From the default display, press the button. e
display will show   .
2. Use the ▲▼ buttons to enter the Technician password
and press SET.
3. e display will show .
4. Press the button until  is displayed; press SET.
5. Use the ▲▼ buttons and scroll to e; press SET.
6. Press the button to scroll to (basic menu); press
SET.
7. Press the button to scroll to h(superheat
setpoint); press SET.
8. Use the ▲▼ buttons to increase or decrease setpoint;
press SET to make the change.
9. To exit and discard changes, press ESC button four
times to return to default display.
Note: Settings that are changed under the Service access will
be discarded once exiting to the default display. For permanent
changes, enter the menu using Administrator password.
19.10 ADJUST DISCHARGE AIR SETPOINT
1. From the default display, press the button. e
display will show   .
2. Use the ▲▼ buttons to enter the Technician password
and press SET.
3. e display will show .
4. Press the button until  is displayed; press SET.
5. Use the ▲▼ buttons and scroll to e; press SET.
6. Press the button to scroll to (basic menu); press
SET.
7. Press the button to scroll to d(discharge air
setpoint); press SET.
8. Use the ▲▼ buttons to increase or decrease setpoint;
press SET to make the change.
9. To exit and discard changes, press ESC button four
times to return to default display.
19.11 MANUALLY POSITION EEV
1. From the default display, press the button. e
display will show   .
2. Use the ▲▼ buttons to enter the Technician password
and press SET.
3. e display will show .
4. Press the button until e is displayed.
5. Press SET to enter the Test sub-menu. e display will
show e(Test Enable).
6. Press SET to enter ON/OFF sub-menu. e display will
show o (Or current state of Test Enable).
7. Press the button to o.
8. Press SET to activate Test Mode. e display will
revert to e.
9. Press the button until  is displayed. Note: for
multiple coil cases 1, 2, 3 may be
shown.
10. Press the SET button. e current EEV % open value
will be displayed.
11. Use the ▲▼ buttons to adjust the desired valve
position.