Bulletin 100-50-9.1 – Page 51
6.10 REMOTE SINGLE EVAPORATOR WITH EEV AND CASE EEPR – CONFIGURATION J
The S3C case controller is capable of controlling and monitoring single temperature, single evaporator refrigerated fixtures
installed as a line-up. The case shown in the diagram below is the lead case of the line-up. In this scenario, one S3C case
controller and one S3C valve module are required. The S3C case controller will control all case functions as well as take all
the desired sensor inputs and drive the EEV. The S3C valve module will drive the EEPR. The typical control method is to
regulate the discharge air temperature of the case evaporator with the EEPR while allowing the EEV to control superheat.
The optional liquid line solenoid (LLS) may be installed as one-per-case or one-per-line-up. In this configuration, each
case in the line-up has its own EEPR connected to the S3C valve module. Case numbers 2, 3, 4,…n will require their own S3C
case controller and valve module as well. All case functions will be synchronized across the line-up in this configuration
with the exception of temperature control.
To configure the S3C control package for configuration J
shown above, follow these directions:
If the controller has not been factory set, then upon initial
start-up, the controller will be in set-up mode and the
screen will display (for self-contained case).
1. Press the SET button, then use ▲▼ buttons to scroll
to o; press SET. is will congure the controller to
support a remote case.
2. Press the
SET
button when
(Rack Identier)
is displayed. Use the ▲▼ buttons to congure the 4
character Rack Identier.
Note: Push
▲
button for
numeric,
▼
for alpha characters.
When satised
with each digit, press the
SET
button to go to the next
digit. Pressing
SET
multiple times will move to the next
parameter.
3. Press the
SET
button when
ud
(Line-up Identier)
is displayed. Use the ▲▼ buttons to congure the 4
character Line-up Identier.
Note: Push
▲
button
for numeric,
▼
for alpha characters.
When
satised with each digit, press the
SET
button to go to
the next digit. Pressing
SET
multiple times will move to
the next parameter.
4. Press the SET button when d (Case Identier)
is displayed. Use the ▲▼ buttons to congure the 4
character Case Identier. Note: Push
▲
button for
numeric,
▼
for alpha characters. When satised
with each digit, press the SET button to go to the next
digit. Pressing SET multiple times will move to the
next parameter.
5. Press the SET button when (Application Type) is
displayed. Use the ▲ button and scroll to (Single
Temperature Case); press SET.
6. Press the SET button when (Local Stepper Valve
Conguration) is displayed. Use the ▲ button to scroll
to (Electronic Expansion Valve); press SET. is
is the valve that is attached to the main S3C Case
Controller.
7. Press the SET button when (Expansion Valve Type)
is displayed. Use ▲▼ buttons to choose the Expansion
Valve Type based on the below chart; press SET.
Display Meaning
u
PULSE WIDTH MODULATION VALVE
5
500 STEP VALVE
1596
1596 STEP VALVE
25
2500 STEP VALVE
3193
3193 STEP VALVE
6386
6386 STEP VALVE
u
CUSTOM STEPPER VALVE (See Section 11)
EEPR (CDS)
Common Suction
CASE
From CASE #n
Liquid
Liquid Line
Solenoid
(optional)
EEV
REMOTE SINGLE EVAPORATOR WITH EEV AND CASE EEPR – CONFIGURATION J