Bulletin 100-50-9.1 – Page 57
6.12  REMOTE MULTIPLE EVAPORATOR WITH 3 EEV – CONFIGURATION L
The S3C case controller is capable of controlling and monitoring single temperature, multiple evaporator refrigerated fixtures 
installed as a line-up. The case shown in the diagram below is the lead case of the line-up. In this scenario, one S3C case controller 
and one S3C valve module are required. The S3C case controller will control all case functions as well as take all the desired 
sensor inputs for one evaporator and drive EEV1. The S3C valve module will take all the desired sensor inputs for the second 
and third evaporators as well as drive both EEV2 and EEV3. The typical control method is to regulate the individual discharge 
air temperature of each evaporator with the EEVs. The optional liquid line solenoid (LLS) may be installed as one-per-case or 
one-per-line-up. Case numbers 2, 3, 4,…n that have two or three evaporators will require their own S3C case controller and S3C 
valve module as well.
If a liquid line solenoid is used, it must be installed on the common liquid line feeding the evaporators and it should be wired into 
the case controller. This configuration only supports Discharge Air control.
To configure the S3C control package for configuration L 
shown above, follow these directions:
If the controller has not been factory set, then upon initial 
start-up, the controller will be in set-up mode and the screen 
will display  (for self-contained case).
1.  Press the SET button, then use ▲▼ buttons to scroll 
to o; press SET. is will congure the controller to 
support a remote case.
2.  Press the 
SET
 button when 
 
(Rack Identier) 
is displayed. Use the ▲▼ buttons to congure the 4 
character Rack Identier. 
Note: Push 
▲
 button for 
numeric, 
▼
 for alpha characters.
 When satised 
with each digit, press the 
SET
 button to go to the next 
digit. Pressing 
SET
 multiple times will move to the next 
parameter.
3.  P
ress the 
SET
 button when 
ud 
(Line-up Identier) 
is displayed. Use the ▲▼ buttons to congure the 4 
character Line-up Identier. 
Note: Push 
▲
 button for 
numeric, 
▼
 for alpha characters.
 When satised 
with each digit, press the 
SET
 button to go to the next 
digit. Pressing 
SET
 multiple times will move to the next 
parameter.
EEV 2
EEV 3
Liquid
Liquid Line
Solenoid
(optional)
EEV 1
CASE
From CASE #n
Common Suction
REMOTE MULTIPLE EVAPORATOR WITH 3 EEVS – CONFIGURATION L