Page 58 – Bulletin 100-50-9.1
4. Press the SET button when d (Case Identier)
is displayed. Use the ▲▼ buttons to congure the 4
character Case Identier. Note: Push
button for
numeric,
for alpha characters. When satised
with each digit, press the SET button to go to the next
digit. Pressing SET multiple times will move to the next
parameter.
5. Press the SET button when  (Application Type) is
displayed. Use the button and scroll to  (Single
Temperature Case); press SET.
6. Press the SET button when  (Local Stepper Valve
Conguration) is displayed. Use the button to scroll to
 (Electronic Expansion Valve); press SET. is is the
valve that is attached to the main S3C Case Controller.
7. Press the SET button when  (Expansion Valve Type)
is displayed. Use ▲▼ buttons to choose the Expansion
Valve Type based on the below chart; press SET.
8. Press the SET button when e (Number of
Evaporators) is displayed. Use the button and scroll to
2(2 Evaporators); press SET.
9. Press the SET button when  (Building Automation
System Expected) is displayed. Use the ▲▼ buttons to
choose e or o; press SET.
a. If e is chosen, the display will show  (Building
Automation System Protocol). Press the SET button
then use ▲▼ buttons to choose the B.A.S. Protocol
based on the below chart; press SET.
10. Press the SET button when o (Month) is shown. Use
the button to choose the current month; press SET.
11. Press the SET button when d (Day) is shown. Use the
button to choose the current day; press SET.
12. Press the SET button when e (Year) is shown. Use the
button to choose the current day; press SET.
13. Press the SET button when e (Time) is shown. Use
the button to choose the current time in 24 hour
format; press SET. Note: Holding the or down
while setting the time will accelerate the scrolling.
14. Press the SET button when ef (Refrigerant Type) is
shown. Use the ▲▼ buttons to choose the Refrigerant
Type; press SET. e list of refrigerants can be seen in
Table on page 99.
15. Press the SET button when  (Number of Cases
Expected in Line-up) is shown. Use the ▲▼ buttons to
choose the number of cases expected in the Line-up;
press SET.
16. Press the SET button when  (Evaporator Pressure
Regulating Valve Type) is shown. Press the button to
scroll to oe (No EEPR); press SET.
17. Press the SET button when d (Discharge Air
Temperature Setpoint) is shown. Use the ▲▼ buttons to
choose the setpoint in °F; press SET.
18. Press the SET button when def (Defrost Type) is
shown. Use the ▲▼ buttons to choose the Defrost Type;
press SET. Defrost options are:
19. Press the SET button when d (Defrost Termination
Temperature Setpoint) is shown. Use the ▲▼ buttons to
choose the setpoint in °F; press SET.
20. Press the SET button when de (Defrost Termination
Fail-safe Time) is shown. Use the ▲▼ buttons to choose
the fail-safe time in minutes; press SET.
21. Press the SET button when dfd (Number of Defrosts
Per Day) is shown. Use the ▲▼ buttons to choose the
defrost per day; press SET.
The S3C Case Control system is now set-up and will begin
controlling the refrigerated display case.
Display Meaning
hg
Hot gas
ee
Electric

Air
Display Meaning
485
Modbus Protocol over RS-485
6485
Bacnet Protocol over RS-485

Bacnet Protocol over IP (Ethernet)
o
Modbus Protocol over IP (Ethernet)
Display Meaning
u
Pulse Width Modulation Valve
5
500 Step Valve
1596
1596 Step Valve
25
2500 Step Valve
3193
3193 Step Valve
6386
6386 Step Valve
u
Custom Stepper Valve (See Section 11)

Table of Contents

Other manuals for Parker Sporlan S3C