Bulletin 100-50-9.1 – Page 99
TABLE 9 BASIC CONFIGURATION MENU
Display Meaning Range Selection Hide Condition
Application Type
Walk-in
Single Temperature Case
Dual Temperature Case (s)
g
du
Case Type: Remote
or Self Contained
Yes
No
e
o
Temperature Control Scheme
Cut-in/Cut-out
Constant On
u
o
Control Temperature
Input Selection
Controlling Return Air
Controlling Discharge Air
d
d
Discharge Air
Temperature Set Point
-30 to 40°F
-3 - 4
(1), (2)
d
Discharge Air Low
Temperature Set Point
-30 to 19°F
-3 -19
(2), (3)
dM
Discharge Air Medium
Temperature Set Point
20 to 50°F
2 - 5
(2), (3)
dd
Discharge Air
Temperature Differential
1 to 10°F
1 -1
(2), (4)
Return Air
Temperature Set Point
-30 to 50°F
-3 - 5
(1), (5)
Return Air Low
Temperature Set Point
-30 to 19°F
-3 - 19
(5), (6)
M
Return Air Medium
Temperature Set Point
20 to 50°F
2 - 5
(5), (6)
d
Return Air Temperature
Differential
1 to 10°F
1 -1
(4), (5)
Superheat Set Point 5 to 45°F
5 -45
(7)
EEPR Control Type
Controlling Pressure
Controlling Temperature
Forced Open
e
(7), (8)
Suction Pressure Set Point 0 to 652 PSIG
- 652
(1), (7), (8), (9)
Low Temperature Suction
Pressure Set Point
0 to 652 PSIG
- 652
(3), (7), (8), (9)
M
Medium Temperature Suction
Pressure Set Point
0 to 652 PSIG
- 652
(3), (7), (8), (9)
o
Minimum On Time 0 to 60 minutes
- 6
(4)
off
Minimum Off Time 0 to 60 minutes
- 6
(4)
Number of Evaporators 1 to 3
1 - 3
(7), (9)
(10), (11)
Number of Cases on Line-up 1 to 8
1 - 8
(12)
Number of Cases on Rack 1 to 32
1 - 32
(12)
Number of Cases in Store 1 to 200
1 - 2
(12)
M
Suction Pressure
Aggregation Mode
Median
Average
Smallest
Largest
Med
u9
g
(7), (8)
(12), (13)
M
Control Temperature
Aggregation Mode
Median
Average
Coldest
Warmest
Med
u9
od
M
(12), (13)