Bulletin 100-50-9.1 – Page 19
5.4.5.2 WIRING
With controller unpowered, carefully route the pressure 
transducer cable to the controller. Take caution to route the 
cable away from sharp edges, fans and defrost heaters. Ensure 
the terminal screws on the controller are backed all the way 
out. Insert the leads of the sensor wire into “Pressure” location 
on the controller, see chart below for sequence. Tighten the 
terminal screws to 3-5 in.-lb. Carefully tug the leads to ensure 
they are secure. See the following figure. Note: If a Case 
Controller and Valve Module are used, the pressure 
transducer may be wired into either controller or two 
pressure transducers may be used for redundancy.
5.4.6   RH/AMBIENT  TEMPERATURE  RHT 
SENSOR
5.4.6.1 MOUNTING
The RHT sensor is required when using pulsed anti-sweat 
heater control. The sensor must be mounted within 10 ft. of 
the case. Position the sensor outside of the case and away from 
periodic air movements such as cooling or heating air vents.
5.4.6.2 WIRING
With controller unpowered, carefully route the RHT cable 
to the controller. Take caution to route the cable away from 
sharp edges. Ensure the terminal screws on the controller 
are backed all the way out. Insert the leads of the sensor 
wire into “Humidity” location on the controller, see chart 
below for sequence. Tighten the terminal screws to 3-5 in.-
lb. Carefully tug the leads to ensure they are secure. See the 
following figure.
5.4.5  SUCTION PRESSURE TRANSDUCER
5.4.5.1 MOUNTING
The suction transducer is required when using an EEV and where superheat calculation is needed. It is also required when 
controlling an EEPR off of pressure. The sensor must be mounted on the suction line after the evaporator as shown below. 
The piping must be horizontal and free draining. Position the sensor at 12 o’clock on the suction line near the coil outlet 
temperature and tighten to 6-8 ft.-lb. Note: Copper gasket is not recommended between Schrader valve and 
transducer. On multi-coil cases, a transducer per evaporator or transducer per case may be used.
Pressure Transducer Cable
Case Control  
or Valve Module
Black 5V
White S
Green Gnd
Coil Outlet
Sensor
Pressure
Transducer
Defrost
Termination Sensor
EEV
10”-14”
minimize
1”- 2” ideal
Evaporator
Refer to the evaporator manufacturer’s 
installation/orientation instructions.
Pressure Range Listed on Label
1/4” SAE Flare Installation 
Torque: 6-8 ft.-lb.
RHT Cable Case Control
Red 5V
Yellow CL
Black Gnd