Bulletin 100-50-9.1 – Page 85
8. Press the SET button when e (Number of
Evaporators) is displayed. Use the ▲ button and scroll
to 1 (1 Evaporator); press SET.
9. Press the SET button when (Building Automation
System Expected) is displayed. Use the ▲▼ buttons to
choose e or o; press SET.
a. If e is chosen, the display will show (Building
Automation System Protocol). Press the SET button
then use ▲▼ buttons to choose the B.A.S. Protocol
based on the below chart; press SET.
10. Press the SET button when o (Month) is shown. Use
the ▲ button to choose the current month; press SET.
11. Press the SET button when d (Day) is shown. Use the
▲ button to choose the current day; press SET.
12. Press the SET button when e (Year) is shown. Use
the ▲ button to choose the current day; press SET.
13. Press the SET button when e (Time) is shown.
Use the ▲ button to choose the current time in 24
hour format; press SET. Note: Holding the ▲ or ▼
down while setting the time will accelerate the
scrolling.
14. Press the SET button when ef (Refrigerant Type) is
shown. Use the ▲▼ buttons to choose the Refrigerant
Type; press SET. e list of refrigerants can be seen in
Table on page 99.
15. Press the SET button when (Number of Cases
Expected in Line-up) is shown. Use the ▲▼ buttons to
choose the number of cases expected in the Line-up;
press SET.
16. Press the SET button when (Evaporator Pressure
Regulating Valve Type) is shown. Use the ▼ button to
scroll to oe(no EEPR); press SET.
17. Press the SET button when (Return Air
Temperature Setpoint) is shown. Use the ▲▼ buttons to
choose the setpoint in °F; press SET.
18. Press the SET button when def (Defrost Type) is
shown. Use the ▲▼ buttons to choose the Defrost Type;
press SET. Defrost options are:
19. Press the SET button when d (Defrost Termination
Temperature Setpoint) is shown. Use the ▲▼ buttons to
choose the setpoint in °F; press SET.
20. Press the SET button when de (Defrost Termination
Fail-safe Time) is shown. Use the ▲▼ buttons to choose
the fail-safe time in minutes; press SET.
21. Press the SET button when dfd (Number of Defrosts
Per Day) is shown. Use the ▲▼ buttons to choose the
defrost per day; press SET.
The S3C Case Control system is now set-up and will begin
controlling the walk-in cooler/freezer.
Display Meaning
hg
Hot gas
ee
Electric
Air
Display Meaning
485
Modbus Protocol over RS-485
6485
Bacnet Protocol over RS-485
Bacnet Protocol over IP (Ethernet)
o
Modbus Protocol over IP (Ethernet)