8.1.3. Regeneration test
1. Check condition of brine tank and any associated equipment.
2. Check salt level in brine tank.
3. Initiate regeneration test.
→ Check brine draw during brine draw stage and make sure of proper function.
→ Check brine tank refill and make sure of proper function.
→ Check operation of safety brine valve, where fitted ***.
→ Check for brine draw off levels.
→ Check for resin loss at the drain during regeneration.
→ Where fitted, check for satisfactory operation of solenoid, i.e. outlet shut off during
regeneration and/or brine line shut off valve(s).
4. Test and record Total Hardness of outlet water from softener.
8.2. Recommended maintenance plan
Items 1 year 2 year 3 year 4 year 5 year
Injector &
filter
Clean Clean Clean Clean
Clean/ replace
if necessary
Refill
controller &
ball **
Clean Clean Clean Clean
Clean/ replace
if necessary
DLFC & ball ** Clean Clean Clean Clean
Clean/ replace
if necessary
Aircheck &
balls ***
- - - -
Clean/ replace
if necessary
Bypass - - - -
Clean/ replace
if necessary
Flappers ** - - - - Replace
Flappers
spring
- - - - Replace
O-rings**
Check for
watertightness
/clean or
replace in case
of leakage
Check for
watertightness
/clean or
replace in case
of leakage
Check for
watertightness
/clean or
replace in case
of leakage
Check for
watertightness
/clean or
replace in case
of leakage
Check for
watertightness
/clean or
replace in case
of leakage
Motor, motor
cable and
optical sensor
harness
Check Check Check Check Replace