Setting Possible values
Starting
value
Increment Lower value Upper
value
Remark
[PUMP]
dosing ↑ dosing ↓
dosing ↑
Mono-directional
control direction
2
[SET]
1.0 mS/
cm
0.001 0.000 uS/cm 2.000 S/cm
[TYPE]
P P
Manual
PID
Controller type
[↳Xp]
0.5 mS/
cm
0.001 0.000 uS/cm 2.000 S/cm P-proportion of
control variable
[↳Ti]
0 s 1 s 0 s 9999 s PID control inte‐
gral action time
(0 seconds = no I-
proportion)
[↳Td]
0 s 1 s 0 s 2500 s PID control deriv‐
ative action time
(0 seconds = no
D-proportion)
[BASIC ]
1
0% 1% - 100% 100% Basic load
[↳MANUAL]
1
0% 1% - 100% 100% Manual control
value
[CHECK‐
TIME]
0 min 1 min 0 min 999 min Control checktime
0 minutes = off
Operating menus