Setting Possible values
Display Starting
value
Increment Lower
value
Upper
value
Remark
[SENSOR]
LFTK1-3m Sensor type
[↳ TYPE]
Conductive Sensor type
[↳ MIN]
0.0 S/cm 0.001 0.000
uS/cm
2.000 S/
cm
Minimum measured
value
[↳ MAX]
0.02 S/cm 0.001 0.000
uS/cm
2.000 S/
cm
Maximum measured
value
[↳ CELLC]
1 cm
-1
0.001 0.006
cm
-1
15 cm
-1
Cell constant
[↳ TMAX]
120 °C 0.01 0.01 °C 150 °C Maximum temperature
that the sensor can
withstand
[↳ PRO‐
FILE]
midCC lowCC, Automatic measuring
range detection
midCC
highCC
[CABLE]
0.25mm² 0.14mm² Cable diameter
0.34mm²
0.25mm²
0.50mm²
[↳ LEN]
3 m 0.01 0 m 50 m Cable length
[↳
R_CABLE]
0.4 Ω 0.01 0 Ω 100 Ω Cable resistance
[TCOMP]
off Temperature compen‐
sation off
lin Linear temperature
compensation
nLF Non-linear tempera‐
ture compensation
(according to DIN EN
27888)