You can reprogram the relays using the
‘Relay’
function in an almost
unlimited way.
You can set whether the respective relay is to switch due to a warning
alert, a fault alert, a pump stroke or to a triggering event of the timer:
Selectable behaviour types
Setting in the
‘Relay’
menu
Effect
Warning The relay switches upon a warning alert (yellow LED*).
Error The relay switches upon a fault alert (red LED*).
Warn.+Error The relay switches upon a warning alert (yellow LED*) or a fault alert (red LED*).
Warn+Err+Stop The relay switches upon a warning alert (yellow LED*) or a fault alert (red LED*)
or a stop (key
[STOP/START]
or pause or bus command).
Stop The relay switches upon a stop (key
[STOP/START]
or pause or command from
an optional module).
Pacing relay The relay switches every stroke.
Option The relay has the option of which module was plugged in (e.g. timer).
* see "Troubleshooting" chapter
You can also indicate how the respective relay should behave as soon as
it switches. You can change this via the setting
‘ENERGIZING (NO)’
/
‘RELEASING (NC).’
The setting option for the ‘Relay’ function only exists if a
relay is present.
Allocations for the relay combinations
Display text "Relay 1" "Relay 2"
(Mechanical relay) Semiconductor relay)
Warning Warning relay Warning relay
Error Fault indicating relay Fault indicating relay
Warn.+Error Warning and fault indicating relay Warning and fault indicating relay
Warn.+Error+Stop Warning, fault indicating and cut-off
relay
Warning, fault indicating and cut-off
relay
Stop Cut-off relay Cut-off relay
Pacing relay - Pacing relay
Set-up
58

Table of Contents