MVI56E-MNETC/MNETCXT ControlLogix Platform Start Here
Modbus TCP/IP Client Enhanced Communication Module - Client/Server User Manual
ProSoft Technology, Inc. Page 17 of 172
September 20, 2018
5 Edit the Module Properties. Select the REQUESTED PACKET INTERVAL value
for scanning the I/O on the module. This value represents the minimum
frequency at which the module will handle scheduled events. This value
should not be set to less than 1 millisecond. The default value is 5
milliseconds. Values between 1 and 10 milliseconds should work with most
applications.
6 Click OK to save the module and close the dialog box. Notice that the module
now appears in the CONTROLLER ORGANIZATION window.