RDM0001/3_2 Page 16 of 70 © 2015 - 2017 Protec Fire Detection plc
8.0 Other Indications
8.1 Power
This indication illuminates when the panel is powered up from mains or batteries.
8.2 Test
This indication illuminates when part or the whole of the panel is in test mode.
8.3 Alarm Routing (Fire Link) Operated
This indication is illuminated when the fire link path has been activated on this panel. This
does not confirm that the fire event has been sent to a remote monitoring centre unless the
confirmation input option has been programmed and the receiving equipment supports this
confirmation feature.
8.4 Fire Protection Operated
This indication is illuminated when the fire protection equipment path has been activated.
This does not confirm that the fire event has been sent to the fire protection equipment
unless the confirmation input option has been programmed and the receiving equipment
supports this confirmation feature.
8.5 Outputs Delayed
This indicator will be illuminated if the commissioning engineer has programmed the system
in a manner that will delay the alarm outputs, the fire link activation or the fire protection
equipment output if the system detects a fire signal. The alarms, fire link or fire protection
equipment output may not activate immediately in the event of a fire.