Chapter 3: Using the Web Interface
251
System Tamper Alarm:
This action causes the BCM2 to show the alarm for the DX tamper
sensor, if any, on the Dashboard page until a person acknowledges it.
By default, this action has been assigned to the built-in tamper
detection event rules. For information on acknowledging an alarm,
see
Dashboard - Alarms
(on page 94).
Actions you can create:
1. Choose Device Settings > Event Rules > .
2. Click the Action field to select an action type from the list.
3. Below is the list of available actions.
Note: The "Change load shedding state" and "Switch outlets" options
are only available for outlet-switching capable models.
Action
Function
Alarm Requires the user to acknowledge the alert
after it is generated. If needed, you can have
the alert notifications regularly generated until
a person takes the acknowledgment action.
See
Alarm
(on page 253).
Change load
shedding state
Enters or quits the load shedding mode. See
Change Load Shedding State
(on page 254).
Execute an action
group
Creates a group of actions comprising existing
actions. See
Action Group
(on page 254).
External beeper Enables or disables the connected external
beeper, or causes it to enter an alarm cycle.
See
External Beeper
(on page 255).
Internal beeper Turns on or off the internal beeper. See
Internal Beeper
(on page 255).
Log event message Records the selected events in the internal log.
See
Log an Event Message
(on page 256).
Push out sensor
readings
Sends internal sensor log, environmental
sensor log or asset management strip data to a
remote server using HTTP POST requests. See
Push Out Sensor Readings
(on page 256).