EasyManua.ls Logo

Rockwell Automation Allen-Bradley Ultra3000

Rockwell Automation Allen-Bradley Ultra3000
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
88 Rockwell Automation Publication 2198-RM003B-EN-P - November 2020
Chapter 6 Application Conversion
Scenario 4: DeviceNet to
I/O Mode
Figure 50 shows the Ultra3000 drive as part of the DeviceNet network. The
Logix Designer application is used for programming the Logix 5000 controller.
The RSNetWorx™ for DeviceNet software is used to configure the DeviceNet
network. This is not required with the Kinetix 5100 drive.
Figure 54 - Ultra3000 DeviceNet Drive in RSLinx® Software
See the DeviceNet Network Configuration User Manual,
publication DNET-UM004
for more details.
Kinetix 5100 uses I/O Mode when migrating Ultra3000 with DeviceNet
communication. In I/O mode, the Kinetix 5100 Add-on Profile (AOP) in the
Logix Designer application provides the Input and Output assemblies for
motion control (position, velocity, torque, and indexing). Additionally, pre-
defined Add-On Instructions are provided to emulate Logix 5000 controller
motion instructions for application programming.
The configuration and Add-On Instruction example are shown in Figure 55
and Figure 56
.

Other manuals for Rockwell Automation Allen-Bradley Ultra3000

Related product manuals