EasyManua.ls Logo

Rockwell Automation Allen-Bradley Ultra3000

Rockwell Automation Allen-Bradley Ultra3000
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82 Rockwell Automation Publication 2198-RM003B-EN-P - November 2020
Chapter 6 Application Conversion
Scenario 1: Analog
Command to Analog
Command
The Analog Input tab in Ultraware software is shown in Figure 47.
Figure 47 - Analog Input Tab in Ultraware
Like Ultraware, KNX5100C software also provides an Analog Speed Input,
Analog Torque Input, and Analog Position Input in the Analog I/O tab. You can
set the Analog Speed, Analog Torque, or Analog Position Command using the
respective tabs shown in Figure 48
. To operate Kinetix 5100 drives with the
Analog Command, the drive operation mode must be set at T (analog torque),
S (analog speed), or PT (analog position) mode (command source ID167 set as
Analog Input) respectively.
Figure 48 - Analog I/O Window in KNX5100C Software

Other manuals for Rockwell Automation Allen-Bradley Ultra3000

Related product manuals