EasyManua.ls Logo

Rockwell Automation PowerFlex 755 Drive

Rockwell Automation PowerFlex 755 Drive
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-14 Using Explicit Messaging
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
PLC-5 Example
Important:The PLC-5 must be Series E (Rev. D.1 or higher) to support
the MultiHop feature that routes messaging to the drive.
Important:Due to inherent limitations with the PCCC N-File method,
only contiguous multiple parameters can be read or written
in one explicit message.
For explicit messaging, the N150 N-Files must be used because they are
already mapped to specific parameters in the drive and its connected
peripherals. This enables direct access to any parameter.
For PCCC N150 N-File information, refer to page C-9
.
PLC-5 Example Ladder Logic Program to Read Single Parameter
A Generic Get Attribute Single message is used to read a single
parameter. This read message example reads the value of the 32-bit
REAL (floating point) parameter 007 - [Output Current] in a PowerFlex
750-Series drive.
Figure 6.15 Example Ladder Logic Explicit Messaging Program for Read Single
Three COP (Copy) instructions are required to convert the 16-bit integer
data table addresses N40:0 (Least Significant Word) and N40:1 (Most
Significant Word) to a 32-bit REAL (floating point) data table address
F102:0 for correct presentation. The first two COP instructions swap
the LSW and MSW, and the third COP instruction correctly presents the
32-bit REAL (floating point) value.

Table of Contents

Related product manuals