42
-
8000B Series
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modi-
cation
Type
F3.03
Proportional
gain 2 of speed
loop
0~100 1 25
F3.04
Integral time 2
of speed loop
0.01~10.00s 0.01s 1.00s
F3.05
High frequency
point of switch
F3.02~F0.10 1Hz 10.00Hz
F3.06
Coefficient
of slip
compensation
at VC control
mode
50~200% 1% 100%
F3.07
Upper limit
torque
0 .0 ~2 0 0 . 0% ( i nv e r t e r r a t ed
current)
0.1% 150.0%
F3.08 Reserved
F3.09 Reserved
F3.10
Pre-alarm
option when
overload
0: Not detect
1: Effective during running and
keep running after alarm
2: E f f e c t i ve d u r i n g r u n nin g
a n d s t o p a f t e r a l a r m (f a u l t
code:E023)
3: Ef fe ct ive du ri ng c on st ant
running and keep running after
alarm
4: Ef f ec ti ve du ri ng c on st ant
running and stop after alarm
1
F3.11
Detecting level
of pre-alarm
when overload
1.0~200.0% (referred to inverter
rated current)
0.1% 150.0%
F3.12
Detecting time
of pre-alarm
when overload
0~600s 1s 1s