36
-
8000B Series
Chapter 5 Function Code Table
Notice:
“○”:
The parameters can be modied at stop or running status.
“◎”:
The parameters cannot be modied at running status.
“●”:
The parameters which are actual-detecting record value cannot be modied.
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modi-
cation
Type
F0 Group: Basic Parameters
F0.00
Control mode
selection
0: Sensorless vector control
1:V/F control
1
●
F0.01
Run command
source
0:Keypad
1:Terminals
2: Communications (RS485)
0
●
F0.02
Setting value
valid or not
of keypad /
terminals
0: Valid and saved when power-
off
1:Valid a nd n ot s av ed w he n
power-off
2: Invalid
3 . Va l i d a t r u n n i n g s t a t u s .
Changed into the setting value
of F0.08 when restart after stop.
0
○
F0.03
Master
frequency
setting source X
0: Up/down key
1: Potentiometer of panel
2: AVI terminal
3: ACI terminal
4: Reserved
5: Reserved
6: Multi-function digital input
terminals
7: PLC
8: PID
9: Communication interface
1
●
F0.04
Auxiliary
frequency
setting source Y
0: AVI terminal
1: ACI terminal
2: Reserved
1
●