60
-
8000B Series
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modi-
cation
Type
FC.04
Communication
timeout fault
time
0.0 (invalid), 0.1~100.0s 0.1s 0.0s
FC.05
Dispose of
communication
timeout fault
0:Alarm and coast to stop
1:No alarm and continue to run
2:No alarm but stop according to
F1.05 (only when F0.01= 2)
3: No alarm but stop according
to F1.05
1
FC.06
Transmission
response action
Unit’s digit:
0: Response to writing
1: No response to writing
Ten’s place:
0:Value not saved when power-
off
1: Value saved when power-off
0
FD Group:Multi-step Speed and Simple PLC Parameters
FD.00
Simple PLC
operation
method
0:Stop after operation once time
1:K ee p the f i na l va lu e af te r
operation once time
2:Operation in cycles
0
FD.01
Memory option
of simple PLC
when power-off
0: Invalid
1:Valid
0
FD.02
Multi- step
speed 0
-100~100% 0.1% 0.0%
FD.03
0
th
step running
time
0.0~6553s(m) 0.1s(m) 0.0s
FD.04
Multi- step
speed 1
-100~100% 0.1% 0.0%
FD.05
1
st
step running
time
0.0~6553s(m) 0.1s(m) 0.0s