39
-
8000B Series
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modi-
cation
Type
F0.25
Cooling fan
running method
(only for 4kW
and above
inverter)
0: Keep running when power on
1: Automatic running
1
F1 Group: Start and Stop Parameters
F1.00 Start mode
0:Start directly
1:DC braking first and then start
2:Speed tracing and start
0
F1.01 Start frequency 0.00~10.00Hz 0.01Hz 1.50Hz
F1.02
Hold time of
start frequency
0.0~50.0s 0.1s 0.0s
F1.03
DC braking
current before
start
0.0~150.0% 0.1% 0.0%
F1.04
DC braking time
before start
0.0~50.0s 0.1s 0.0s
F1.05 Stop mode
0: Deceleration to stop
1: Coast to stop
0
F1.06
Starting
frequency of DC
braking
0.00~ F0.10 0.01Hz 0.00Hz
F1.07
Waiting time
before DC
braking
0.0~50.0s 0.1s 0.0s
F1.08
DC braking
current
0.0~150.0% 0.1% 0.0%