8000B Series
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modi-
cation
Type
F8.12 FDT level 0.00~F0.10 0.01Hz 50.00Hz
F8.13 FDT lag 0.0~100.0% 0.1% 5.0%
F8.14
Detecting range
of reached
frequency
0.0~100.0% (Maxi. frequency) 0.1% 0.0%
F8.15
Braking
threshold
voltage
115.0~140.0% (standard DC bus
voltage)
0.1% 120.0%
F8.16
Speed display
coefficient
0.1~999.9% 0.1% 100.0%
8.17
Start/stop
selection when
running time is
over
0:Keep running
1:Stop
0
F8.18
Running time
setting
0~9999h 1h 9999
F8.19 Droop control 0.00Hz~10.00Hz 0.01Hz 0.00Hz
F8.20
Panel filter time
selection
0.00~10.00s 0.01s 0.10s
F8.21
Output delay
time selection
0~9999s 0.1s 0.0s
F8.22
Lower limit
of frequency
detecting
0.00~Maxi. frequency 0.01Hz 20.00Hz
F8.23
Upper limit
of frequency
detecting
0.00~Maxi. frequency 0.01Hz 40.00Hz
F8.24 Reserved