12 Appendix
12.1 Function block lists
CO1: Heating circuit Rk1 (not system Anl 1.9)*
F Function WE Anl
Comments
Function block parameters/Range of values (default setting)
01 Room sensor RF1 0 Not in Anl
1.5, 1.6,
3.x
CO1 -> F01 - 1: Temperature display and input FG1 for
Type 5244/5257-5 Room Panel active
TROVIS 5570 Room Panel:
CO1 -> F01 - 1 and CO7 -> F03 - 1
02 Outdoor sensor
AF1
0 1.5, 1.6 CO1 -> F02 - 1: Weather-compensated control active
Outdoor temperature received over device bus:
CO1 -> F02 - 1 and CO7 -> F07 - 1
1 Not in Anl
1.5, 1.6
03 Return flow sensor
RüF1
0 1.2 CO1 -> F03 - 1: Sensor and limiting function active
Function block parameter:
Limiting factor / 0.1 to 10.0 (1.0)
1 Not in Anl
1.2
04 Reserved
05 Underfloor heating
Drying of jointless
floors
0 Not in Anl
1.5, 1.6,
3.x
CO1 -> F05 - 1: Limitation of the adjustment ranges
Function block parameters:
Temperature rise / 1 to 10 °C/24 h (5 °C/24 h)
Maximum temperature / 25 to 60 °C (45 °C)
Maintaining time of max. temperature /1 to 10 days (1 day)
Temperature reduction / 0 to 10 °C/ 24 h (0 °C / 24 h)
START
06 Reserved
07 Optimization 0 Not in Anl
1.5, 1.6,
3.x
CO1 -> F07 - 1: Only with • CO1 -> F01 - 1
• CO1 -> F02 - 1
08 Adaptation 0 Not in Anl
1.5, 1.6,
3.x
CO1 -> F08 - 1: Only with • CO1 -> F01 - 1
• CO1 -> F02 - 1
• CO1 -> F11 - 0
09 Flash adaptation 0 Not in Anl
1.5, 1.6,
3.x
CO1 -> F09 - 1 Only with CO1 -> F01 - 1
Function block parameter:
Cycle time / 1 to 100 min (20 min)
Gain K
p
/ 0 to 25 (0)
10 Reserved
102 EB 5575 EN
Appendix