EasyManua.ls Logo

Samson TROVIS 5575 - Three-Step Control; On;Off Control; Releasing a Control Circuit over the Binary Input

Samson TROVIS 5575
138 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.6 Three-step control
The flow temperature can be controlled using a PI algorithm. The valve reacts to pulses that
the controller emits upon an existing system deviation. The length of the first pulse, in particu
-
lar, depends on the extent of the system deviation and the selected
Proportional gain K
P
(the
pulse length increases as K
P
increases). The pulse and pause lengths change continuously un
-
til the system deviation has been eliminated. The pause length between the single pulses is
greatly influenced by the
Reset time T
N
(the pause length increases as T
N
increases).
The
Valve transit time T
Y
specifies the time required by the valve to travel through the range
of 0 to 100 %.
Functions
WE Configuration
Control type
three-step
1
2.0
120 s
45 s
CO1, 2, 4 -> F12 - 1, Rk_
K
P
(proportional gain) / 0.1 to 50.0
T
N
(reset time) / 1 to 999 sec
T
Y
(valve transit time) / 5, 10,15, …, 240 sec
7.7 On/off control
The flow temperature can be controlled, for example, by activating and deactivating a
boiler. The controller switches on the boiler when the flow temperature falls below the set
point by T = 0.5 x
hysteresis
. When the set point is exceeded by T = 0.5 x
hysteresis
, the
boiler is switched off again. The greater the value you choose for
Hysteresis
, the lower will
be the activation/deactivation frequency. By setting the
Minimum ON time
, an activated
boiler remains switched on during this period regardless of the flow temperature fluctuations.
Similarly, a deactivated boiler will remain switched off regardless of the flow temperature
fluctuations if the
Min. OFF time
has been specified.
Functions
WE Configuration
Control type
on/off
1
5 °C
2 min
2 min
CO1, 2, 4 -> F12 - 0
Hysteresis / 1 to 30 °C
Min. ON time / 0 to 10 min
Min. OFF time / 0 to 10 min
7.8 Releasing a control circuit over the binary input
The release of a control circuit using the binary output only becomes effective when the re
-
spective control circuit is in automatic operating mode (icon ). The released control circuit
always works in automatic mode; the deactivated control circuit behaves as if it were trans
-
ferred to stand-by mode.
EB 5575 EN 77
System-wide functions

Table of Contents

Related product manuals