Functions
WE Configuration
Room sensors RF1/2 0 CO1, 2 -> F01 - 1
Outdoor sensors AF1 1 CO1 -> F02 - 1
Optimization 0 CO1, 2 -> F07 - 1
Parameters
WE Rotary switch / Range of values
Day set point 20 °C Top, middle/0to4C
Night set point 15 °C Top, middle/0to4C
5.8 Flash adaptation
To achieve that the controller reacts immediately to room temperature deviations during
rated or reduced operation, adjust the function block setting CO1, 2 -> F09 - 1.
The heating is then always switched off as soon as the room temperature exceeds the
Day set
point
or
Night set point
by 2 °C.
Heating first starts again when the room has cooled off and the room temperature is 1 °C
above the
Set point
. The flow temperature set point is corrected if the
Cycle time
and
Gain K
p
are set to a value other than 0. The
Cycle time
determines the intervals at which the flow tem-
perature set point is corrected by 1 °C. A
Gain K
p
set to a value other than 0 causes a direct
increase/decrease in flow temperature set point when a sudden deviation in room tempera-
ture arises. A
Gain K
p
setting of 10.0 is recommended.
Note!
Cooling loads, such as drafts or open windows, affect the control process!
Rooms may be temporarily overheated when the cooling load has been eliminated!
Functions
WE Configuration
Room sensors RF1/2 0 CO1, 2 -> F01 - 1
Flash adaptation 0
20 min
0
CO1, 2 -> F09 - 1
Cycle time / 1 to 100 min
K
p
(gain) / 0 to 25
Parameters
WE Rotary switch / Range of values
Day set point 20 °C Top, middle/0to4C
Night set point 15 °C Top, middle/0to4C
60 EB 5575 EN
Functions of the heating circuit