5.4 Deactivation depending on outdoor temperature
5.4.1 OT deactivation value in rated operation
If the outdoor temperature exceeds the limit entered in
OT deactivation value in rated opera
-
tion
, the heating circuit concerned is put out of service immediately. The valve is closed and the
pump is switched off after t = 2 x valve transit time. Heating operation is restarted immediately
when the outdoor temperature falls below this value (less 0.5 °C hysteresis).
With the default settings, this means that, during the warm season, the system is switched off at
an outdoor temperature of 22 °C.
Parameter
WE Parameter level / Range of values
OT deactivation value
in rated operation
22 °C PA1, 2 / 0 to 50 °C
5.4.2 OT deactivation value in reduced operation
If the outdoor temperature exceeds the limit value
OT deactivation value in reduced operation
,
the heating circuit concerned is put out of service immediately. The valve is closed and the
pump is switched off after t = 2 x valve transit time. Heating operation is restarted immediately
when the outdoor temperature falls below this value (less 0.5 °C hysteresis).
With the default settings, this means that, at night, the system is switched off at an outdoor
temperature of 15 °C to save energy. Nevertheless, remember that the system requires some
time in the morning to heat up the building.
Parameter
WE Parameter level / Range of values
OT deactivation value
in reduced operation
15 °C PA1, 2 / –20 to 50 °C
5.4.3 OT activation value in rated operation
If a heating circuit is in reduced operation (automatic operating mode), the circuit is auto
-
matically transferred to rated operation when the outdoor temperature falls below the limit
value
OT activation value in rated operation
. When the limit value is exceeded (plus 0.5 °C
hysteresis), reduced operation is restarted.
This function is activated at very low temperatures to avoid that the building cools down ex
-
cessively outside the times-of-use when low outdoor temperatures occur.
Parameter
WE Parameter level / Range of values
OT activation value
in rated operation
–15 °C PA1, 2 / –20 to 5 °C
56 EB 5575 EN