12.2 Parameter lists
PA1 ( ): Parameter level Rk1
PA2 ( ): Parameter level Heating circuit Rk 2
Display
Parameter designation
Range of values (default setting)
Gradient, flow
0.2 to 3.2 (1.8)
(with CO1, 2 -> F05 - 1: 0.2 to 1.0 (1.0) applies)
Level (parallel shift)
–30 to 30 °C (0 °C)
Min. flow temperature
5 to 130 °C (20 °C)
Max. flow temperature
5 to 130 °C (90 °C)
(with CO1, 2 -> F05 - 1: 5 to 50 °C (50 °C) applies)